Backflow assembly test: Golden Animal Hospital
ApprovedFiled Mar 23, 2024 by Hayden Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 23, 2024
- Assembly type
- RP
- Serial number
- K800193
- Size
- 1
- Test gauge serial
- G-4471
- Gauge calibration date
- May 28, 2023
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Lindqvist, current on the service date
- All required fields present
- Address matches parcel 085-32-01326
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.