Backflow assembly test: Golden Diner

Approved

Filed Apr 23, 2023 by Hayden Danner, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 23, 2023
Assembly type
DC
Serial number
A523421
Size
2
Test gauge serial
G-4148
Gauge calibration date
Nov 24, 2022
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 085-57-01225
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.