Back to the backflow review queue

Backflow assembly test: Crossroads Brewing Co

Approved

Filed May 13, 2025 by Jordan Nguyen, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 13, 2025
Assembly type
RP
Serial number
K700016
Size
4
Test gauge serial
G-6373
Gauge calibration date
Jan 10, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-91-01146
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7742 Pine Knoll Way
Owner: Marsh Holdings LLC
Parcel 085-91-01146