Backflow assembly test: 5272 Mill Creek Trl

Approved

Filed Mar 5, 2025 by Drew Ramirez, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Mar 5, 2025
Assembly type
PVB
Serial number
Z835387
Size
1
Test gauge serial
G-9038
Gauge calibration date
Sep 7, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 085-27-01156
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5272 Mill Creek Trl
Owner: Emerson Ashby
Parcel 085-27-01156