Back to the backflow review queue

Backflow assembly test: 5277 Pine Knoll Dr

Approved

Filed Jun 14, 2024 by Hayden Lindqvist, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 14, 2024
Assembly type
PVB
Serial number
W332669
Size
3/4
Test gauge serial
G-2195
Gauge calibration date
May 1, 2024
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 085-62-01135
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5277 Pine Knoll Dr
Owner: Blake Ellery
Parcel 085-62-01135