Back to the backflow review queue

Backflow assembly test: 6358 Mill Creek Ct

Sent back

Filed Nov 23, 2026 by Jordan Nguyen, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 23, 2026
Assembly type
RP
Serial number
B519392
Size
3/4
Test gauge serial
G-6744
Gauge calibration date
Sep 25, 2026
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-39-01052
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Sent back Please add the test gauge calibration certificate.

Property

6358 Mill Creek Ct
Owner: Rowan Danner
Parcel 085-39-01052