Back to the backflow review queue

Backflow assembly test: 354 Turkey Hill Ln

Approved

Filed Aug 11, 2026 by Logan Danner, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 11, 2026
Assembly type
RP
Serial number
A771378
Size
1
Test gauge serial
G-9937
Gauge calibration date
Nov 18, 2025
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Danner, current on the service date
  • All required fields present
  • Address matches parcel 085-29-01117
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

354 Turkey Hill Ln
Owner: Casey Fairley
Parcel 085-29-01117