Backflow assembly test: Riverside Market

Approved

Filed Aug 7, 2025 by Cameron Nguyen, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Aug 7, 2025
Assembly type
DC
Serial number
B312494
Size
1 1/2
Test gauge serial
G-1942
Gauge calibration date
Jun 13, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 085-25-01280
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.