Back to the backflow review queue

Backflow assembly test: 3990 Meadow Lark Ct

Filed Nov 19, 2026 by Drew Ramirez, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 19, 2026
Assembly type
DC
Serial number
B919977
Size
3/4
Test gauge serial
G-1533
Gauge calibration date
Jan 7, 2026
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 085-40-01106
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

3990 Meadow Lark Ct
Owner: Parker Stroud
Parcel 085-40-01106