Backflow assembly test: 1953 Meadow Lark Way

Approved

Filed Oct 6, 2025 by Morgan Brandt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Oct 6, 2025
Assembly type
PVB
Serial number
B754515
Size
1
Test gauge serial
G-2543
Gauge calibration date
Jul 6, 2025
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-32-01006
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1953 Meadow Lark Way
Owner: Morgan Whitcomb
Parcel 093-32-01006