Backflow assembly test: 9396 Cedar Hollow Ct
ApprovedFiled Feb 11, 2025 by Sam Benton, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Feb 11, 2025
- Assembly type
- DC
- Serial number
- B865212
- Size
- 1
- Test gauge serial
- G-3729
- Gauge calibration date
- Jun 30, 2024
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Benton, current on the service date
- All required fields present
- Address matches parcel 093-47-01226
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.