Back to the backflow review queue

Backflow assembly test: 8489 Spring Branch Rd

Approved

Filed Nov 8, 2026 by Jamie Ashby, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Nov 8, 2026
Assembly type
RP
Serial number
K647637
Size
1
Test gauge serial
G-5652
Gauge calibration date
Apr 8, 2026
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Ashby, current on the service date
  • All required fields present
  • Address matches parcel 093-11-01355
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8489 Spring Branch Rd
Owner: Sam Ramirez
Parcel 093-11-01355