Backflow assembly test: 3886 Spring Branch Ln
ApprovedFiled Sep 10, 2026 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 10, 2026
- Assembly type
- RP
- Serial number
- B406337
- Size
- 3/4
- Test gauge serial
- G-7582
- Gauge calibration date
- May 19, 2026
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Relief valve opened at
- 4.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-83-01036
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3886 Spring Branch Ln
Owner: Jamie Hollins
Parcel 093-83-01036