Backflow assembly test: Station Apartments
ApprovedFiled Oct 14, 2025 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 14, 2025
- Assembly type
- RP
- Serial number
- Z205186
- Size
- 2
- Test gauge serial
- G-9925
- Gauge calibration date
- Sep 11, 2025
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-13-01340
- Readings in range, no flags
- Result: passing. Next due date resets when approved.