Back to the backflow review queue

Backflow assembly test: 1949 Sycamore Ct

Approved

Filed Aug 5, 2026 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 5, 2026
Assembly type
RP
Serial number
K999393
Size
1
Test gauge serial
G-6213
Gauge calibration date
Jun 16, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 093-83-01090
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1949 Sycamore Ct
Owner: Sam Pruitt
Parcel 093-83-01090