Backflow assembly test: 4781 Fox Run Way

Approved

Filed Jul 21, 2024 by Sam Danner, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Jul 21, 2024
Assembly type
RP
Serial number
Z946884
Size
1
Test gauge serial
G-7305
Gauge calibration date
May 13, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Danner, current on the service date
  • All required fields present
  • Address matches parcel 093-22-01079
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.