Back to the backflow review queue

Backflow assembly test: 141 Stone Gate Ln

Approved

Filed Sep 14, 2024 by Morgan Brandt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Sep 14, 2024
Assembly type
RP
Serial number
Z280360
Size
3/4
Test gauge serial
G-2015
Gauge calibration date
May 13, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-32-01352
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

141 Stone Gate Ln
Owner: Avery Hollins
Parcel 093-32-01352