Backflow assembly test: 5097 Quarry Dr

Approved

Filed Aug 30, 2024 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 30, 2024
Assembly type
RP
Serial number
K597343
Size
1
Test gauge serial
G-2025
Gauge calibration date
Jul 14, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Vance, current on the service date
  • All required fields present
  • Address matches parcel 093-34-01234
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5097 Quarry Dr
Owner: Parker Whitcomb
Parcel 093-34-01234