Backflow assembly test: Station Medical Offices
ApprovedFiled May 14, 2025 by Morgan Brandt, Lakeside Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- May 14, 2025
- Assembly type
- RP
- Serial number
- B896901
- Size
- 1 1/2
- Test gauge serial
- G-3772
- Gauge calibration date
- Sep 2, 2024
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Brandt, current on the service date
- All required fields present
- Address matches parcel 093-31-01356
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9222 Stone Gate Ln
Owner: Nguyen Holdings LLC
Parcel 093-31-01356