Back to the backflow review queue

Backflow assembly test: 5097 Quarry Dr

Approved

Filed Aug 15, 2025 by Morgan Brandt, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Aug 15, 2025
Assembly type
RP
Serial number
K597343
Size
1
Test gauge serial
G-8537
Gauge calibration date
Nov 16, 2024
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 093-34-01234
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5097 Quarry Dr
Owner: Parker Whitcomb
Parcel 093-34-01234