Backflow assembly test: 9642 Sycamore Ct

Approved

Filed May 14, 2024 by Sam Danner, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 14, 2024
Assembly type
PVB
Serial number
W446974
Size
3/4
Test gauge serial
G-8439
Gauge calibration date
Dec 1, 2023
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Danner, current on the service date
  • All required fields present
  • Address matches parcel 093-49-01285
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.