Backflow assembly test: Two Rivers Bakery

Approved

Filed Oct 24, 2026 by Reese Hollins, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Oct 24, 2026
Assembly type
RP
Serial number
Z437245
Size
4
Test gauge serial
G-2422
Gauge calibration date
Jul 23, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Hollins, current on the service date
  • All required fields present
  • Address matches parcel 093-10-01138
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.