Backflow assembly test: Golden Pizza

Approved

Filed Nov 28, 2024 by Sam Danner, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 28, 2024
Assembly type
RP
Serial number
B393674
Size
1 1/2
Test gauge serial
G-2865
Gauge calibration date
Jul 14, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Danner, current on the service date
  • All required fields present
  • Address matches parcel 093-52-01041
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.