Back to the backflow review queue
Backflow assembly test: 2429 Old Church Way
ApprovedFiled Jan 14, 2024 by Drew Vance, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 14, 2024
- Assembly type
- PVB
- Serial number
- A279159
- Size
- 3/4
- Test gauge serial
- G-4293
- Gauge calibration date
- Sep 29, 2023
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-58-01212
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
2429 Old Church Way
Owner: Jamie Ashby
Parcel 093-58-01212