Backflow assembly test: 1106 Ridgeview Ct

Approved

Filed Dec 25, 2024 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 25, 2024
Assembly type
RP
Serial number
W629948
Size
3/4
Test gauge serial
G-1923
Gauge calibration date
May 19, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ashby, current on the service date
  • All required fields present
  • Address matches parcel 095-29-01314
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1106 Ridgeview Ct
Owner: Avery Calloway
Parcel 095-29-01314