Backflow assembly test: 1106 Ridgeview Ct
ApprovedFiled Dec 30, 2025 by Quinn Ashby, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 30, 2025
- Assembly type
- RP
- Serial number
- W629948
- Size
- 3/4
- Test gauge serial
- G-4516
- Gauge calibration date
- May 29, 2025
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ashby, current on the service date
- All required fields present
- Address matches parcel 095-29-01314
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1106 Ridgeview Ct
Owner: Avery Calloway
Parcel 095-29-01314