Back to the backflow review queue

Backflow assembly test: Blue Heron Elementary School

Approved

Filed Mar 18, 2026 by Reese Whitcomb, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 18, 2026
Assembly type
DC
Serial number
K324688
Size
1
Test gauge serial
G-1044
Gauge calibration date
Apr 8, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 095-76-01205
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2290 Ridgeview Ln
Owner: Stroud Holdings LLC
Parcel 095-76-01205