Backflow assembly test: Corner Pizza
ApprovedFiled Oct 3, 2024 by Reese Whitcomb, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 3, 2024
- Assembly type
- RP
- Serial number
- W618823
- Size
- 1
- Test gauge serial
- G-9162
- Gauge calibration date
- Jun 20, 2024
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Whitcomb, current on the service date
- All required fields present
- Address matches parcel 095-39-01001
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.