Back to the backflow review queue
Backflow assembly test: 9147 Old Church Trl
Needs reviewFiled Nov 23, 2026 by Reese Whitcomb, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2026
- Assembly type
- DC
- Serial number
- A187395
- Size
- 3/4
- Test gauge serial
- G-6417
- Gauge calibration date
- Jul 22, 2026
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Whitcomb, current on the service date
- All required fields present
- Address matches parcel 095-56-01243
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
9147 Old Church Trl
Owner: Riley Calloway
Parcel 095-56-01243