Back to the backflow review queue

Backflow assembly test: 4466 Mill Creek Ct

Approved

Filed Jan 22, 2026 by Rowan Danner, Keystone Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 22, 2026
Assembly type
RP
Serial number
B661988
Size
3/4
Test gauge serial
G-2211
Gauge calibration date
Nov 24, 2025
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Danner, current on the service date
  • All required fields present
  • Address matches parcel 095-46-01299
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4466 Mill Creek Ct
Owner: Riley Brandt
Parcel 095-46-01299