Backflow assembly test: 3263 Hickory Ln

Approved

Filed Jan 21, 2025 by Morgan Benton, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jan 21, 2025
Assembly type
RP
Serial number
K833517
Size
1
Test gauge serial
G-9926
Gauge calibration date
May 17, 2024
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Benton, current on the service date
  • All required fields present
  • Address matches parcel 095-77-01041
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.