Backflow assembly test: 3291 Sycamore Rd
ApprovedFiled Sep 3, 2026 by Drew Lindqvist, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 3, 2026
- Assembly type
- RP
- Serial number
- A385500
- Size
- 1
- Test gauge serial
- G-3371
- Gauge calibration date
- Apr 9, 2026
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Lindqvist, current on the service date
- All required fields present
- Address matches parcel 097-27-01050
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.