Back to the backflow review queue

Backflow assembly test: 5708 Meadow Lark Way

Approved

Filed Nov 2, 2024 by Drew Lindqvist, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 2, 2024
Assembly type
DC
Serial number
K529386
Size
1
Test gauge serial
G-7096
Gauge calibration date
Aug 26, 2024
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 097-30-01042
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5708 Meadow Lark Way
Owner: Quinn Nguyen
Parcel 097-30-01042