Back to the backflow review queue

Backflow assembly test: 2994 Orchard Way

Approved

Filed Dec 17, 2025 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 17, 2025
Assembly type
RP
Serial number
B809850
Size
3/4
Test gauge serial
G-4282
Gauge calibration date
Jul 13, 2025
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-31-01262
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2994 Orchard Way
Owner: Emerson Stroud
Parcel 097-31-01262