Backflow assembly test: 8061 Laurel Ct
ApprovedFiled Apr 28, 2024 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 28, 2024
- Assembly type
- RP
- Serial number
- B219323
- Size
- 3/4
- Test gauge serial
- G-8697
- Gauge calibration date
- Jul 31, 2023
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-33-01285
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
8061 Laurel Ct
Owner: Jordan Calloway
Parcel 097-33-01285