Back to the backflow review queue

Backflow assembly test: 2354 Pine Knoll Trl

Approved

Filed Oct 6, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 6, 2025
Assembly type
PVB
Serial number
A361317
Size
3/4
Test gauge serial
G-9281
Gauge calibration date
Jul 1, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-17-01342
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2354 Pine Knoll Trl
Owner: Cameron Okafor
Parcel 097-17-01342