Backflow assembly test: 2354 Pine Knoll Trl
ApprovedFiled Oct 17, 2026 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 17, 2026
- Assembly type
- PVB
- Serial number
- A361317
- Size
- 3/4
- Test gauge serial
- G-6811
- Gauge calibration date
- Mar 30, 2026
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ramirez, current on the service date
- All required fields present
- Address matches parcel 097-17-01342
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2354 Pine Knoll Trl
Owner: Cameron Okafor
Parcel 097-17-01342