Back to the backflow review queue
Backflow assembly test: 8113 Orchard Way
ApprovedFiled Sep 22, 2026 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 22, 2026
- Assembly type
- PVB
- Serial number
- Z299593
- Size
- 1
- Test gauge serial
- G-4807
- Gauge calibration date
- Dec 16, 2025
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Kessler, current on the service date
- All required fields present
- Address matches parcel 097-43-01107
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8113 Orchard Way
Owner: Taylor Fairley
Parcel 097-43-01107