Backflow assembly test: 237 Meadow Lark Ct
ApprovedFiled Jun 3, 2026 by Taylor Whitcomb, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 3, 2026
- Assembly type
- RP
- Serial number
- W643655
- Size
- 3/4
- Test gauge serial
- G-5871
- Gauge calibration date
- Dec 26, 2025
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Whitcomb, current on the service date
- All required fields present
- Address matches parcel 097-59-01282
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.