ApprovedFiled Aug 6, 2023 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 6, 2023
- Assembly type
- RP
- Serial number
- K806709
- Size
- 3/4
- Test gauge serial
- G-7654
- Gauge calibration date
- May 13, 2023
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 4.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Stroud, current on the service date
- All required fields present
- Address matches parcel 097-12-01029
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.