Backflow assembly test: 8770 Ridgeview Trl
ApprovedFiled Jul 24, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 24, 2025
- Assembly type
- PVB
- Serial number
- K625766
- Size
- 3/4
- Test gauge serial
- G-4092
- Gauge calibration date
- Jan 6, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ramirez, current on the service date
- All required fields present
- Address matches parcel 097-78-01281
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.