Back to the backflow review queue

Backflow assembly test: 6760 Old Church Ct

Approved

Filed Dec 24, 2023 by Drew Okafor, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 24, 2023
Assembly type
RP
Serial number
Z259195
Size
1
Test gauge serial
G-8105
Gauge calibration date
Oct 10, 2023
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Okafor, current on the service date
  • All required fields present
  • Address matches parcel 097-25-01297
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6760 Old Church Ct
Owner: Logan Marsh
Parcel 097-25-01297