Backflow assembly test: 6760 Old Church Ct

Approved

Filed Feb 1, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 1, 2025
Assembly type
RP
Serial number
Z259195
Size
1
Test gauge serial
G-9891
Gauge calibration date
Jun 24, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-25-01297
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.