Back to the backflow review queue

Backflow assembly test: 6760 Old Church Ct

Approved

Filed Feb 19, 2026 by Logan Stroud, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 19, 2026
Assembly type
RP
Serial number
Z259195
Size
1
Test gauge serial
G-7973
Gauge calibration date
Dec 27, 2025
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 097-25-01297
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6760 Old Church Ct
Owner: Logan Marsh
Parcel 097-25-01297