Backflow assembly test: 8712 Meadow Lark Ct

Approved

Filed Oct 16, 2026 by Drew Lindqvist, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 16, 2026
Assembly type
DC
Serial number
A418764
Size
3/4
Test gauge serial
G-5538
Gauge calibration date
Jan 14, 2026
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 097-42-01049
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8712 Meadow Lark Ct
Owner: Casey Marsh
Parcel 097-42-01049