Backflow assembly test: 5498 Fox Run Ln
ApprovedFiled Aug 1, 2026 by Drew Lindqvist, Ridge Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 1, 2026
- Assembly type
- PVB
- Serial number
- B386413
- Size
- 1
- Test gauge serial
- G-4792
- Gauge calibration date
- Feb 19, 2026
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Lindqvist, current on the service date
- All required fields present
- Address matches parcel 097-68-01355
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5498 Fox Run Ln
Owner: Jamie Whitcomb
Parcel 097-68-01355