Back to the backflow review queue
Backflow assembly test: 6433 Sycamore Rd
ApprovedFiled Aug 27, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 27, 2025
- Assembly type
- DC
- Serial number
- A515814
- Size
- 3/4
- Test gauge serial
- G-9756
- Gauge calibration date
- Feb 10, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Ramirez, current on the service date
- All required fields present
- Address matches parcel 097-81-01348
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6433 Sycamore Rd
Owner: Alex Pruitt
Parcel 097-81-01348