Backflow assembly test: 1926 Sycamore Dr

Approved

Filed Mar 11, 2026 by Taylor Whitcomb, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Mar 11, 2026
Assembly type
RP
Serial number
B993796
Size
1
Test gauge serial
G-9301
Gauge calibration date
Jan 5, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Relief valve opened at
2.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 097-98-01037
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.