Back to the backflow review queue

Backflow assembly test: Main Street Self Storage

Approved

Filed Oct 26, 2025 by Drew Okafor, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 26, 2025
Assembly type
RP
Serial number
B729564
Size
1 1/2
Test gauge serial
G-2636
Gauge calibration date
Jul 20, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Okafor, current on the service date
  • All required fields present
  • Address matches parcel 097-96-01139
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9087 Mill Creek Trl
Owner: Brandt Holdings LLC
Parcel 097-96-01139