Back to the backflow review queue

Backflow assembly test: 7036 Stone Gate Trl

Approved

Filed Mar 30, 2026 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 30, 2026
Assembly type
DC
Serial number
K420117
Size
1
Test gauge serial
G-9603
Gauge calibration date
Nov 28, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-55-01114
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7036 Stone Gate Trl
Owner: Reese Calloway
Parcel 097-55-01114